Products

    Pages

        DIN-THSTAT

        Heating, Cooling, and Relative Humidity Thermostat, DIN Rail Mount

        The DIN‑THSTAT is a DIN‑rail mountable heating, cooling, and relative‑humidity thermostat. The DIN‑THSTAT provides control of radiant floor heat, forced air, and heat pump HVAC systems. DIN rail mounting allows for installation in an equipment cabinet, keeping the living area free from a wall-mounted thermostat. Small, unobtrusive remote temperature and humidity sensors1 gather the environmental conditions from the room and transmit the data to the DIN‑THSTAT.

        The DIN‑THSTAT is a versatile heating, cooling and relative‑humidity thermostat that provides control of radiant floor heat, forced air, and heat pump HVAC systems. DIN rail mounting allows for installation in an equipment cabinet, keeping the living area free from a wall‑mounted thermostat. Small, unobtrusive remote temperature and humidity sensors1 gather the environmental conditions from the room and transmit the data to the DIN‑THSTAT.

        A Crestron control system connection allows temperature adjustments from virtually anywhere by using a Crestron touch screen, handheld remote, mobile app, or computer.

        Remote Sensors
        The CHV‑RTS and CHV‑RTHS remote sensors provide indoor temperature and humidity data so that the DIN‑THSTAT can be installed out of view. The CHV‑RSS monitors outdoor climate and floor temperature, enabling outdoor low-temperature compensation to prevent condensation on windows during cold weather. The DIN‑THSTAT accepts up to three temperature sensors. Each sensor connects via a single twisted pair wire.

        Auxiliary Ports
        Auxiliary ports allow state sensing from HVAC equipment and interfacing with additional HVAC devices.

        DIN Rail Mounting
        The DIN‑THSTAT snaps onto a standard DIN rail for installation in a wall mount enclosure (Crestron DIN‑EN series or similar1) or on a wall panel. The DIN‑THSTAT is designed to mount in a DIN‑EN‑2X18‑HC‑OPEN, DIN‑EN‑3X18‑HC‑OPEN, or DIN‑EN‑6X18‑HC‑OPEN for an attractive centralized mounting solution. The hinged cover provides easy access to equipment wiring while openings in the cover provide access to the DIN modules through the cover.

        Cresnet Communications
        The DIN‑THSTAT communicates with a Crestron control system (such as the DIN‑AP3) via the Cresnet control network. A pair of Cresnet ports is provided on the DIN‑THSTAT to allow easy daisy‑chaining of several DIN‑THSTAT or Crestron DIN rail devices.

         
        Key Features
        • Works with Crestron® remote temperature sensors (sold separately)
        • Operates as part of a complete Crestron automation system (sold separately)
        • Onboard controls for system setup and testing
        • System integration via Cresnet® communications
        • Cresnet powered (24 VDC)
        • 9U 35 mm DIN rail mountable
        • Backlit LCD display
        • Front panel controls for setup, temperature, and humidity adjustments
        1. Item(s) sold separately.
        2. Outdoor temperature measurement is -30° to 120° F (-34° to 49° C) if thermistor sensors are used.
        3. The setpoint range can be decreased during device configuration.
        4. Each temperature sensor requires a dedicated low-capacitance twisted pair wire (<7 nF per run) and supports a wire length of 500 ft (152 m) using CAT5. Thermostat wire is not recommended, but may be used if necessary at lengths up to 100 ft (30 m).

        This product may be purchased from select authorized Crestron dealers and distributors. To find a dealer or distributor, please contact the Crestron sales representative for your area. A list of sales representatives is available online at www.crestron.com/How-To-Buy/Find-a-Representative or by calling 855‑263‑8754.

        This product is covered under the Crestron standard limited warranty. Refer to www.crestron.com/warranty for full details.

        The specific patents that cover Crestron products are listed online at patents.crestron.com.

        Certain Crestron products contain open source software. For specific information, please visit www.crestron.com/opensource.

        Crestron, the Crestron logo, 3‑Series, Cresnet, and infiNET EX are either trademarks or registered trademarks of Crestron Electronics, Inc. in the United States and/or other countries. Other trademarks, registered trademarks, and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Crestron disclaims any proprietary interest in the marks and names of others. Crestron is not responsible for errors in typography or photography. Specifications are subject to change without notice. ©2020 Crestron Electronics, Inc.

         
        CrestronHome
        Measurement Range (Supplied by Remote Sensor)
        Indoor Temperature 32° to 110° F (0° to 43° C)
        Outdoor Temperature -40° to 170° F (-40° to 77° C)2
        Humidity 0% to 100% RH
        Temperature Tolerance
        ±1° F (±0.5° C)
        Humidity Tolerance
        ±5%
        Setpoint Range3
        Auto Setpoint 38° to 99° F (3° to 37° C)
        Heat Only Setpoint 38° to 89° F (3° to 32° C)
        Cool Only Setpoint 59° to 99° F (15° to 37° C)
        Humidity Setpoint 5% to 90% RH
        Power
        Cresnet Power Usage 3 W (125 mA @ 24 VDC)
        Controls
        Keypad (1) 5-way navigation pad for menu navigation and temperature/humidity adjustments
        HOME (1) pushbutton, returns to the previous screen or the home screen
        BACK (1) pushbutton, steps menu back one level
        Display
        Type RGB LCD
        Size (diagonal) 1.80 in (46 mm)
        Resolution 176 x 220
        Function Front panel display to view temperature and humidity settings;
        Used for local configuration
        Communications
        Cresnet Cresnet slave mode
        Connections
        Y1, Y2, Y3 (1) Compressor stage 1, 2, and 3
        G (1) Fan relay
        B (1) Active in non-cool modes
        O (1) Active in cool mode
        RC (1) Reference cool
        RH (1) Reference heat
        W1, W2, W3 (1) Heat stage 1, 2, and 3
        HUM (1) Humidity call switch power
        AUX1, AUX2 (2) Output relay to interface with other HVAC devices
        AUX-IN (1) Signal from HVAC state sensing or other custom programming
        TS1, TS2 & G (2) From remote temperature sensor (CHV-RTS), remote slab sensor (CHV-RSS), or remote temperature and humidity sensor (CHV-RTHS) and (2) ground4 Also compatible with 10k thermistors. All sensors and thermistors are sold separately.
        TS3 & G (1) From outdoor remote temperature sensor and (1) ground4 Also compatible with 10k thermistors. All sensors and thermistors are sold separately.
        24 Y Z G (2) 4-pin detachable terminal blocks;
        Cresnet slave port with hardwire parallel pass-through
        USB (1) Micro B female, USB 2.0 computer console port for firmware download
        INTERFACE For future use
        Construction
        Housing Plastic
        Mounting 35 mm DIN EN 60715 rail mount, DIN 43880 form factor for enclosures with 45 mm front panel cutout, occupies 9 DIN module spaces (162 mm)
        Environmental
        Temperature 32° to 104° F (0° to 40° C)
        Humidity 10% to 90% RH (noncondensing)
        Heat Dissipation 10 BTU/hr maximum;
        For indoor use only
        Dimensions
        Height 3.68 in (94 mm)
        Width 6.33 in (161 mm)
        Depth 2.34 in (60 mm)
        Weight
        13 oz (363 g)
        Compliance
        CE, IC, FCC Part 15 Class B digital device
        Click here to search product certificates.
        1. Item(s) sold separately.
        2. Outdoor temperature measurement is -30° to 120° F (-34° to 49° C) if thermistor sensors are used.
        3. The setpoint range can be decreased during device configuration.
        4. Each temperature sensor requires a dedicated low-capacitance twisted pair wire (<7 nF per run) and supports a wire length of 500 ft (152 m) using CAT5. Thermostat wire is not recommended, but may be used if necessary at lengths up to 100 ft (30 m).

        This product may be purchased from select authorized Crestron dealers and distributors. To find a dealer or distributor, please contact the Crestron sales representative for your area. A list of sales representatives is available online at www.crestron.com/How-To-Buy/Find-a-Representative or by calling 855‑263‑8754.

        This product is covered under the Crestron standard limited warranty. Refer to www.crestron.com/warranty for full details.

        The specific patents that cover Crestron products are listed online at patents.crestron.com.

        Certain Crestron products contain open source software. For specific information, please visit www.crestron.com/opensource.

        Crestron, the Crestron logo, 3‑Series, Cresnet, and infiNET EX are either trademarks or registered trademarks of Crestron Electronics, Inc. in the United States and/or other countries. Other trademarks, registered trademarks, and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Crestron disclaims any proprietary interest in the marks and names of others. Crestron is not responsible for errors in typography or photography. Specifications are subject to change without notice. ©2020 Crestron Electronics, Inc.

        Pricing Region Select
        Please select your region below to see the appropriate Advertised Pricing.