Building Management Systems Interface; requires factory configuration, programming and start-up. Please contact Crestron Sales Support Services.
This product has been discontinued. Please contact Crestron True Blue Support at 1-888-CRESTRON for a replacement solution or more information.
A must have for large scale integration projects that require interconnectivity between the Crestron control system and other building systems.
BACnet/IP support is NOW AVAILABLE for the MC3 3-Series Control System.
The GLA-BMS is an Ethernet based "protocol translator" which allows a Crestron system to communicate directly with any number of building management protocols. Programmable like any other Crestron Ethernet device, the GLA-BMS makes it easy to interface with:
- BACnet®/IP[1]
- BACnet®/MSTP (RS-485)
- Modbus® TCP/IP
- Modbus® RTU (RS-485)
- LonWorks®
- Metasys® N2 Open (Johnson Controls)
This product is available as part of a complete engineered Crestron Green Light® system. Please contact Sales Support Services for more information.
Key Features
- Interfaces Crestron systems with building management systems
- Native Crestron Ethernet communications
- Compatible with a wide range of protocols
- Supports BACnet, Modbus, LonWorks, and Metasys N2
| Connections |
| |
Ethernet |
10BaseT RJ45 |
| |
Serial |
RJ45 (RS-232) Terminal (RS-485) |
| Power Requirements |
| |
24 VAC floating; 9-30 VDC @ 5W |
| Mounting |
| |
Desktop, Wall, DIN Rail |
| Environmental |
| |
Temperature |
32° to 144°F (0° to 60°C) |
| |
Humidity |
10% to 95% RH (non-condensing) |
| Dimensions |
| |
Height |
2 in (5.1 cm) |
| |
Depth |
3.9 in (9.9 cm) |
| |
Width |
3.9 in (9.9 cm) |
| Standards & Certifications |
| |
UL Listed, CE Marked, FCC tested to comply with FCC part 15, ODVA Ethernet/IP Conformance Tested |