Fluorescent Dimmer - Operates Hi-Lume FDB ballasts, controls 4 zones, 120VAC

Discontinued

This product has been discontinued. Please contact Crestron True Blue Support at 1-888-CRESTRON for a replacement solution or more information.

The CNLFDB-4 dimming module provides 4 channels of dimming for fluorescent lighting fixtures equipped with Lutron® Hi-lume® or Eco-10™ three-wire electronic fluorescent dimming ballasts. The CNLFDB-4 occupies a single module space in any CSTC cabinet, or two spaces in a CLC-6 cabinet. The unit is designed to communicate with the PAC2 control system, or any Crestron control system, via the Cresnet control network.

The CNLFDB-4 dimming module provides 4 channels of dimming for fluorescent lighting fixtures equipped with Lutron® Hi-lume® or Eco-10™ three-wire electronic fluorescent dimming ballasts. The CNLFDB-4 occupies a single module space in any CSTC cabinet, or two spaces in a CLC-6 cabinet. The unit is designed to communicate with the PAC2 control system, or any Crestron control system, via the Cresnet control network.

 
 
Load Ratings
  Dimmer Channels 4
  Per Channel 16 Amps
  Module Total 64 Amps
  Load Types Hi-lume FDB or Eco-10 ECO 3-wire electronic fluorescent dimming ballasts
  Load Control Phase-controlled dimming signal plus air-gap relay
  Relay Rating 20 Amp at 277 Volts AC, 1HP at 125 Volts AC
Power Requirements
  Line Power 120 or 277 Volts AC, 60Hz, single-phase;
All feeds must be same phase
  Cresnet Power Usage 4 Watts (0.17 Amp @ 24 Volts DC)
Connectors
  NET (1) 4-pin 5mm detachable terminal block;
Cresnet slave port, connects to Cresnet control network
  L-IN 1 - 4 (4) Captive screw terminals, line power inputs
  L-OUT 1 - 4 (4) Captive screw terminals, switch outputs
  DIM 1 - 4 (4) Captive screw terminals, dimmer outputs
  NEUT (1) Captive screw terminal, neutral
Controls
  ID CODE (2) Rotary DIP Switches, set Cresnet ID
  NORMAL/OVERRIDE (1) Slide switch, OVERRIDE forces all channels to full on
LED Indicators
  NET POWER Indicates DC power supplied from Cresnet network
  ACTIVITY Indicates communication with Cresnet system
  Channels 1 – 4 Indicate each relay is energized
Environmental
  Temperature 32° to 104°F (0° to 40°C)
  Humidity 10% to 90% RH (non-condensing)
  Heat Dissipation 17 BTU/Hr + (0.3 BTU/Hr x Load Current in Amps) + (0.02 per ballast), 40 BTU/Hr at maximum load
Enclosure
  Occupies 2 module spaces in a CLC-6 cabinet (order optional MTPL-02074-1 space plate);
Occupies 1 module space in a CSTC cabinet
Weight
  3.5 lbs (1.59 kg)